The pre-assembled, ready-to-connect blowdown unit with conductive sensor is used for automatic control of the salt content in the circulating water of cooling and humidifier circuits. The functions of the control system include blowdown, enabling of the circulation pump and control of up to three dosing pumps (1x volume-controlled for hardness stabilizer, 2x time-controlled with monthly timer for biocide 1 and 2). Thanks to the built-in micro SD card (4 GB), data logging is possible in accordance with the 42nd BImSchV.

Benefits

  • Operating message for one of the four functions (blowdown, circulation pump, volume- or time-proportional dosing)
  • Warning/fault messages are immediately visible due to the colour change in the display
  • Blowdown valve (motorized ball valve) is closed when de-energized, no risk of the system running empty in the event of a power failure
  • Data from micro SD card easy to read out

Applications

  • For controlling cycles of concentration in open cooling circuits or air humidifiers and for controlling up to three dosing pumps (1x volume-controlled for hardness stabilizer, 2x time-controlled with monthly timer for biocide 1 and 2)

Controller :
Cooltrol data
Cabel length:
2 m
Reference temperature:
25 °C
Output blowdown valve:
Mains voltage, max. 4 A
Output volume-prop. dosing:
open collector
Output time-prop. dosing 1/2:
floating, max. 250 V AC / 3 A
Warning output:
floating, max. 250 V AC / 3 A
Fault output:
floating, max. 250 V AC / 3 A
Protection class:
IP 65
Operating signal:
floating, max. 250 V AC / 3 A
Current output:
4 - 20 or 0 - 20 mA active
Conditions of use:
The unit may only be used to control or measure conductivity in open cooling circuits and humidifiers and for dosing biocides in water-bearing systems.
Operating pressure:
0.2 – 6.0 bar
Operating temperature:
0 – 40 °C
 
 
Enquire for more information
please weait… Your data is being loaded...

Article no. Product name Measuring range
mS/m
Hydraulic connection
supply / return / blowdown
Blowdown valve Blowdown flow rate
m³/h at ∆p 0.6 bar
Mains connection
V / Hz
Cell constant C
00170156 Cooltrol data K (MKB 15) K = 1.0
Single article
Cooltrol data K (MKB 15) K = 1.0 10 – 500 DN 20 / DN 20 / DN 15 MKB 15 4.0 100 - 240 / 50 - 60 1.0
00170163 Cooltrol data K (MKB 20) K=1.0
Single article
Cooltrol data K (MKB 20) K=1.0 10 – 500 DN 20 / DN 20 / DN 20 MKB 20 6,5 100 - 240 / 50 - 60 1.0
00170162 Cooltrol data K (MKB 25) K=1.0
Single article
Cooltrol data K (MKB 25) K=1.0 10 – 500 DN 25 / DN 25 / DN 25 MKB 25 13.5 100 - 240 / 50 - 60 1.0
00170170 Cooltrol data K (MKB 15) K=0.1
Single article
Cooltrol data K (MKB 15) K=0.1 0.5 – 10 DN 20 / DN 20 / DN 15 MKB 15 4.0 100 - 240 / 50 - 60 0.1
00170173 Cooltrol data K (MKB 20) K=0.1
Single article
Cooltrol data K (MKB 20) K=0.1 0.5 – 10 DN 20 / DN 20 / DN 20 MKB 20 6.5 100 - 240 / 50 - 60 0.1
00170172 Cooltrol data K (MKB 25) K=0.1
Single article
Cooltrol data K (MKB 25) K=0.1 0.5 – 10 DN 25 / DN 25 / DN 25 MKB 25 13.5 100 - 240 / 50 - 60 0.1